Rate Control Inputs - Baer DLX User Manual

Table of Contents

Advertisement

3.7.3

Rate control inputs

The rate control inputs TR1 to TR4 determine (if desired and if present in
the customer specific hardware configuration) the currently active energy
rate and maximum demand rate. The usage of inputs and the correlation of
input states to rates can be programmed freely (settable).
The factory default settings use TR1 to switch between two energy and
demand rates.
Energy rate mask
Demand rate mask
The state of deactivated control inputs (in our example: TR2, TR3 and
TR4) has no influence on the rate control (no matter whether the state
is 0 = open or 1 = closed).
If other combinations are desired, they can be programmed (see user man-
ual of DLXPARA).
Example: rate control for 4 energy rates and 2 demand rates, controlled by TR1, TR2
and TR3.
Energy rate mask
Demand rate mask
32
TR1
TR2
TR3
TR1
TR2
TR3
0
-
-
1
-
-
TR1
TR2
TR3
TR1
TR2
TR3
0
0
0
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
TR4
TR4
Energy
Demand
-
AT1
MT1
-
AT2
MT2
TR4
TR4
Energy
Demand
-
AT1
MT1
-
AT1
MT2
-
AT2
MT1
-
AT2
MT2
-
AT3
MT1
-
AT3
MT2
-
AT4
MT1
-
AT4
MT2