NOTE
• Information on blade terminals
Commercially available products (as of January 2017)
Phoenix Contact Co., Ltd.
Terminal screw
size
M2
NICHIFU Co., Ltd.
Terminal screw
size
M2
• When using a blade terminal (without insulation sleeve), take caution that the twisted wires do not come out.
• Connection terminal compatibility table
Encoder cable
PA1
PA2
PB1
PB2
FR-A8AP terminal
PZ1
PZ2
PG
SD
 Wiring example
• Speed control
Standard motor with encoder, 5 V differential line driver
To converter unit
Forward rotation start
Reverse rotation start
Contact input common
3
Frequency command
2
Frequency setting
potentiometer
1
1/2W1kΩ
Torque limit
(+)
command
(-)
(±10V)
Cable gauge
2
(mm
)
With insulation sleeve
0.3
AI 0,34-6TQ
0.5
AI 0,5-6WH
Cable gauge
Blade terminal part No. Insulation cap part No.
2
(mm
)
0.3 to 0.75
BT 0.75-7
FR-V7CBL
PA
Do not connect anything to this.
PB
Do not connect anything to this.
PZ
Do not connect anything to this.
PG
SD
Inverter
U
P/+
V
N/-
W
Earth
STF
(Ground)
FR-A8AP
STR
PA1
PA2
SD
PB1
PB2
10
Differential
PZ1
PZ2
2
Complementary
5
PG
SD
Terminating
resistor ON
PG
1
∗3
SD
(+)
∗6
OFF
∗4
Ferrule part No.
Without insulation
sleeve
A 0,34-7
A 0,5-6
VC 0.75
FR-JCBL
PA
PAR
PB
PBR
PZ
PZR
5E
AG2
Vector control dedicated motor, 12 V
Motor with
encoder
U
V
IM
Inverter
W
E
∗1
C
FR-A8AP
R
A
N
Differential
PLG
B
Complementary
P
∗2
Terminating
resistor
H
K
OFF
5VDC power supply
(-)
∗5
2.8 Connection to a motor with encoder (Vector control)
Crimping tool
name
CRIMPFOX 6
Crimping tool
model No.
NH 69
complementary
Vector control
dedicated motor
U
U
V
V
IM
W
W
E
Earth
(Ground)
∗1
PA1
A
PA2
B
PB1
C
PB2
D
PLG
F
PZ1
PZ2
∗2
G
PG
S
SD
R
PG
ON
∗3
SD
12VDC power
∗4
∗6
(-)
∗5
(+)
supply
2. INSTALLATION AND WIRING
1
2
3
4
5
6
7
8
9
10
67