Mitsubishi Electric 800 Series Hardware Instruction Manual page 33

Separated converter type
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Installation of the inverter on the enclosure
Push the inverter heat sink part outside the enclosure, and fix the inverter to the panel with upper and lower installation frames.
NOTE
• As the heat sink part protruded through the panel includes a cooling fan, this type of installation is not suitable for the
environment of water drops, oil, mist, dust, etc.
• Be careful not to drop screws, dust etc. into the inverter and cooling fan section.
32
2. INSTALLATION AND WIRING
2.3 Installation of the inverter and enclosure design
Enclosure
Inside the
Exhausted air
enclosure
Inverter
Installation
frame
Cooling
Dimension of
wind
the outside of
185mm
the enclosure
There are finger guards behind the enclosure.
Therefore, the thickness of the panel should be
less than 10 mm (∗1) and also do not place
anything around finger guards to avoid contact
with the finger guards.
Enclosure
∗1
10mm
140mm
Finger guard