Mitsubishi Electric 800 Series Hardware Instruction Manual page 47

Separated converter type
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Output signal
Terminal
Type
Terminal name
symbol
A1,
Relay output 1 (fault
B1,
output)
*1
C1
A2,
B2,
Relay output 2
*1
C2
*1
Inverter running
RUN
*1
Up to frequency
SU
*1
Overload alarm
OL
*1
Open collector output
IPF
*1
Frequency detection
FU
Open collector output
SE
common
For meter
*2
FM
NPN open collector
output
AM
Analog voltage output
*3
Analog current output
CA
*1
Terminal functions can be selected using Pr.190 to Pr.196 (Output terminal function selection).
*2
Terminal FM is provided in the FM-type inverter.
*3
Terminal CA is provided in the CA-type inverter.
 Communication
46
2. INSTALLATION AND WIRING
2.6 Control circuit
Terminal function description
1 changeover contact output that indicates that an inverter's protective
function has been activated and the outputs are stopped.
Fault: discontinuity across B and C (continuity across A and C), Normal:
continuity across B and C (discontinuity across A and C)
1 changeover contact output
The output is in LOW state when the inverter output frequency is equal to
or higher than the starting frequency (initial value: 0.5 Hz). The output is
in HIGH state during stop or DC injection brake operation.
The output is in LOW state when the output
frequency is within the set frequency range ±10%
(initial value). The output is in HIGH state during
acceleration/deceleration and at a stop.
The output is in LOW state when stall prevention
is activated by the stall prevention function. The
output is in HIGH state when stall prevention is
canceled.
No function is assigned in the initial setting. Use
Pr.192 to assign a function to the terminal.
The output is in LOW state when the inverter
output frequency is equal to or higher than the
preset detection frequency, and is in HIGH state
when it is less than the preset detection
frequency.
Common terminal for terminals RUN, SU, OL, IPF, FU
Among several monitor items such as output
frequency, select one to output it via these
terminals. The signal is not output during an
inverter reset.
The size of output signal is proportional to the
magnitude of the corresponding monitor item.
Use Pr.55, Pr.56, and Pr.866 to set full scales for
the monitored output frequency, output current,
and torque.
Rated specification
Contact capacity: 230
VAC 0.3 A
(power factor = 0.4), 30
VDC 0.3 A
Permissible load: 24
VDC (27 VDC at
maximum) 0.1 A
(The voltage drop is
2.8 V at maximum
while the signal is ON.)
The open collector
transistor is ON
Fault code (4 bits)
(conductive) in LOW
output.
state.
The transistor is OFF
(not conductive) in
HIGH state.
Permissible load
Output item:
current: 2 mA, pulse
output frequency
for full scale: 1440
(initial setting)
pulses/s
This terminal can be
Maximum output
used for open
pulse: 50k pulses/s,
collector outputs by
permissible load
setting Pr.291.
current: 80 mA
Output signal: 0 ±10
VDC,
permissible load
current: 1 mA
(load impedance 10 kΩ
Output item:
or more), resolution: 8
output frequency
bits
(initial setting)
Load impedance: 200
to 450 Ω,
output signal: 0 to 20
mADC