2.5.4

Applicable cables and wiring length

Select a recommended size cable to ensure that the voltage drop ratio is within 2%.
If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit will cause the motor torque to
decrease especially at a low speed.
The following tables show a selection example for the wiring length of 20 m (at 440 V input power supply).
• Converter unit (FR-CC2)
Converter
Terminal
model FR-
screw
*4
CC2-H-[]
size
315K
M12 (M10)
355K
M12 (M10)
400K
M12 (M10)
450K
M12 (M10)
500K
M12 (M10)
560K
M12 (M10)
630K
M12 (M10)
• Inverter (ND rating)
Inverter
Terminal
model FR-
screw
*4
A842-[]
size
07700(315K) M12 (M10)
08660(355K) M12 (M10)
09620(400K) M12 (M10)
10940(450K) M12 (M10)
12120(500K) M12 (M10)
• Inverter (SLD rating)
Inverter
Terminal
model FR-
screw
*4
A842-[]
size
07700(315K) M12 (M10)
08660(355K) M12 (M10)
09620(400K) M12 (M10)
10940(450K) M12 (M10)
12120(500K) M12 (M10)
• Inverter (LD rating)
Inverter
Terminal
model FR-
screw
*4
A842-[]
size
07700(315K) M12 (M10)
08660(355K) M12 (M10)
09620(400K) M12 (M10)
10940(450K) M12 (M10)
12120(500K) M12 (M10)
40
2. INSTALLATION AND WIRING
2.5 Main circuit terminals
Crimp
terminal
Tightening
torque
(N·m)
R/L1, S/L2,
R/L1, S/L2,
T/L3
46
150-12
2×150
46
C2-200
2×200
46
C2-200
2×200
46
C2-250
2×250
46
C2-200
3×200
46
C2-200
3×200
46
C2-200
3×200
Crimp
terminal
Tightening
torque
(N·m)
U, V, W
46
150-12
2×150
46
C2-200
2×200
46
C2-200
2×200
46
C2-250
2×250
46
C2-250
2×250
Crimp
terminal
Tightening
torque
(N·m)
U, V, W
46
C2-200
2×200
46
C2-250
2×250
46
C2-250
2×250
46
C2-200
3×200
46
C2-200
3×200
Crimp
terminal
Tightening
torque
(N·m)
U, V, W
46
C2-200
2×200
46
C2-200
2×200
46
C2-250
2×250
46
C2-250
2×250
46
C2-200
3×200
2
*1
HIV cables, etc. (mm
)
Earthing
P/+, N/-
(grounding)
T/L3
cable
2×150
100
2×200
100
2×200
100
2×250
100
3×200
2×100
3×200
2×100
3×200
2×100
2
*1
HIV cables, etc. (mm
)
Earthing
U, V, W
P/+, N/-
(grounding)
cable
2×150
100
2×200
100
2×200
100
2×250
100
3×200
2×100
2
*1
HIV cables, etc. (mm
)
Earthing
U, V, W
P/+, N/-
(grounding)
cable
2×200
100
2×250
100
3×200
2×100
3×200
2×100
3×200
2×100
2
*1
HIV cables, etc. (mm
)
Earthing
U, V, W
P/+, N/-
(grounding)
cable
2×200
100
2×200
100
2×250
100
3×200
2×100
3×200
2×100
Cable gauge
AWG/
PVC cables, etc. (mm
*2
MCM
R/L1, S/L2,
R/L1, S/L2,
T/L3
T/L3
2×300
2×150
2×350
2×185
2×400
2×185
2×500
2×240
2×500
2×240
3×350
3×185
3×400
3×185
Cable gauge
AWG/
PVC cables, etc. (mm
*2
MCM
U, V, W
U, V, W
2×300
2×150
2×350
2×185
2×400
2×185
2×500
2×240
2×500
2×240
Cable gauge
AWG/
PVC cables, etc. (mm
*2
MCM
U, V, W
U, V, W
2×400
2×185
2×500
2×240
2×500
2×240
3×350
3×185
3×400
3×185
Cable gauge
AWG/
PVC cables, etc. (mm
*2
MCM
U, V, W
U, V, W
2×350
2×185
2×400
2×185
2×500
2×240
2×500
2×240
3×350
3×185
2
*3
)
Earthing
(grounding)
cable
150
2×95
2×95
2×120
2×120
2×150
2×150
2
*3
)
Earthing
(grounding)
cable
150
2×95
2×95
2×120
2×120
2
*3
)
Earthing
(grounding)
cable
2×95
2×120
2×120
2×150
2×150
2
*3
)
Earthing
(grounding)
cable
2×95
2×95
2×120
2×120
2×150