Earthing - Festo Compact Performance CPV Series Manual

Cpv valve terminal with direct link for the sds (smart distributed system)
Table of Contents

Advertisement

1. Installation
1
n.c. (not con
nected)
2
24 V DC load volt
age for CPV
valves
3
0 V load voltage
for CPV valves
4
n.c. (not con
nected)
Fig. 1/9: Pin assignment of the load voltage connection

1.3.5 Earthing

Festo P.BE−CP−SD8−...−EN en 0503b
3
4
The CPV valve terminal has its own earthing/ground connec
tion on the left−hand end plate.
Please note
S Connect the earth/ground connection of the left−hand
end plate with low impedance (short cable with large
cross−sectional area) to the earth potential.
You will thereby avoid interference as a result of electro−
magnetic influences.
Example of connection
Observe the following when connecting the 24V load voltage
supply (pin 2):
The tolerance 21 V ... 26.4 V DC must be observed.
S
Use a cable with sufficient cross−sectional area to connect
S
the earth connection on the CPV valve terminal.
2