Festo Compact Performance CPV Series Manual page 20

Cpv valve terminal with direct link for the sds (smart distributed system)
Table of Contents

Advertisement

1. Installation
Baud rate
Max. number of CPV valve terminals
Up to 500 kBaud
Over 500 kBaud
Fig. 1/3: Automatic mode: Summary of possible station numbers with automatic mode
1−8
4. Press key F1 Address: NONE. The following menu will
appear:
−−
Select Device
Address: NONE
Enter: STAT sS ESC
<Digit>
ENT
5. Press the STAT key. The Activator will now search for the
station number. When you commission the CPV valve ter
minal the first time, station number 126 will appear, other
wise the station number last saved.
6. You can accept the station number found by pressing the
ENTER key. You can continue the search with
7. Now enter the new station number (ENT).
Please note
S The CPV valve terminal must be marked with the station
number last saved.
In this way you can be sure that, if the CPV valve terminal
has to be replaced, the station number is known and can
be loaded into the new CPV valve terminal.
64
32
Please note
Station numbers may only be assigned once for each field
bus line.
−−
Permitted station number
1; ...; 126
1; ...; 126
Festo P.BE−CP−SD8−...−EN en 0503b
sS
.