Section 5
Protection and control engineering
82
Binary
BIO
Inputs
Binary
BIO
Outputs
RTD/ mA Inputs
Analog
Inputs/
Outputs
mA Outputs
GOOSE
IEC 61850
GOOSERCV/ SMVRCV
(input side)
SMV
IEC 61850 9-2 LE
GUID-800BDCFA-E6A2-42A3-9370-0EEF76156E70 V1 EN
Figure 60:
Signal Matrix: operation principles
A binary input channel can be connected to one or more function block inputs. If a
binary input channel is connected to several different function blocks in the
Application Configuration tool, the connection appears as glue logic in Signal Matrix.
A binary output channel can only be activated from one function block output. If it is
activated from more than one function block output, the glue logic has to be used.
Glue logic means inserting a logical gate (OR and AND blocks) between the binary
input and the function blocks or between the function blocks and the binary output
channel. This can be engineered with Signal Matrix.
1MRS759117 A
FBs
FBs
FBs
GOOSERCV
(input side)
FBs
SMVRCV
(input side)
REX640