1MRS759117 A
7.3.1.2
REX640
Engineering Manual
GUID-FC5EA780-2535-49EC-9321-AA37CB41DEFB V1 EN
Figure 114:
Selecting the SCL file version
6.
Click Export to generate the SCD file.
A progress window shows the ongoing export of the station.

Exporting ICD or CID files

1.
Select the IED in the Plant Structure view.
2.
Right-click the IED and select Export.
3.
In the Export dialog box, from the Save as type list, select the type of file to
export.
Configured IED description (.cid) for the IEC 61850 structure as needed
for the IED at runtime
IED capability description (.icd) for the IEC 61850 structure
GUID-9E366488-5110-4C4A-89BF-551B7AD71E14 V1 EN
Figure 115:
IEC 61850: Selecting the IED file type for export
4.
Click Save.
5.
In the SCL Export Options dialog box, select the export options.
IEC 61850 communication engineering