Engineering Manual
GUID-F32A9920-F1AC-475F-9291-DA41F75FF285 V1 EN
Figure 99:
Setting colors for the different symbol states
If custom symbols have been used in the SLD configuration and then deleted, the
symbol graphics show an error and all the related connections are removed from the
configuration.

Creating SLD pages

1.
On the Graphical Display Editor toolbar, select the symbol standard from the
drop-down list.
IEC
ANSI
2.
Ensure that the Snap to grid and Show grid functions are available.
These are the default and recommended settings when designing a single-line
diagram.
3.
Place the primary equipment on the single-line diagram approximately in the
wanted position.
If required, rotate the symbols using the Rotate Left or Rotate Right functions.
4.
Consider the necessary symbol connections, that is, links.
4.1. Click on the source port and click on the desired position to add a
connection point.
4.2. Draw a perpendicular line by moving the mouse while pressing SHIFT and
clicking on the target port.
5.
Connect the symbols where necessary.
5.1. Move the mouse pointer over the symbol's connection ports.
Section 6
LHMI engineering
119