1MRS759117 A
REX640
Engineering Manual
do not match, PCM600 informs about the mismatch with a
dialog box.
GUID-B0A82B47-680D-4CB7-AED4-668AD5C2FD6F V1 EN
Figure 29:
Selecting the composition code
4.
On the Configuration selection page, select the configuration type and click
Next.
•
Select Empty configuration to create an empty configuration.
•
Select Import configuration from file (PCMI/PCMT) to import an
example configuration.
Click Browse to select the .pcmi/.pcmt file that has the example
configuration.
•
Select Default configuration (available only for IEC 61850 Edition 2)
to generate a default configuration.
If a default configuration is selected, the next page is skipped as
default configuration is only supported for the IEC 61850
Edition 2 IEDs. To configure an IEC 61850 Edition 1 IED, select
Section 4
Setting up a project