Searching For Events And Alarms; Saving Hmi Alarm And Fault Selection; Virtual Programmable Leds; Configuring Virtual Programmable Leds - ABB RELION REX640 Engineering Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759117 A
6.3.1.2
6.3.1.3
6.3.2
6.3.2.1
REX640
Engineering Manual
Select the check box in the column header of a column in the data
grid view to modify the alarm configuration, priority or fault
selection of all events.

Searching for events and alarms

In HMI Event Filtering, locate an event or alarm in the event filtering or alarm
selection views in one of the alternative ways.
Use the predefined search strings.
Type a search string manually.

Saving HMI alarm and fault selection

Save the HMI alarm and fault selection in one of the alternative ways.
On the File menu, select Save.
Click Save on the toolbar.
The Save button on the toolbar is activated when the configuration is
modified.

Virtual programmable LEDs

Configuring virtual programmable LEDs

Three steps must be completed to enable programmable LEDs in the relay's HMI.
1.
Instantiate at least one LED and connect the OK and ALARM signals in
application configuration.
2.
Clear all events elevated as alarms in HMI Event Filtering so that the HMI Home
button LED can follow the programmable LED state instead of the alarm list.
3.
Add the Programmable LEDs page to the relay's page list in Graphical Display
Editor.
When these steps are completed and the new configuration is successfully
written to the relay, the states of the configured virtual programmable LEDs are
shown on the programmable LEDs page.
Section 6
LHMI engineering
129

Advertisement

Table of Contents
loading

Table of Contents