ABB RELION REX640 Engineering Manual page 147

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759117 A
[1] Applicable when using IET600
REX640
Engineering Manual
tool. For larger projects it is recommended to use IET600, which is available as a
standalone tool.
1.
Create a project in IET600.
2.
Import the SCD file created by PCM600.
3.
Conduct vertical communication engineering (monitoring direction).
3.1. Check the default data sets.
3.2. Configure the default data sets.
3.3. Configure additional Report Control Blocks when needed for each data
set used for vertical communication.
3.4. Link the IED clients to the Report Control Blocks.
4.
Conduct horizontal communication engineering.
4.1. Configure GOOSE control blocks for each data set configured for GOOSE
messages.
4.2. Define the client IEDs for each GOOSE control block.
4.3. Link the IEDs to the GOOSE control block that must receive the GOOSE
control block.
5.
Export the updated SCD file.
All data sets, Report Control Blocks and GOOSE control blocks
must be located in LLN0.
IEC 61850 communication engineering
[1]
[1]
Data sets meant for vertical reporting can only contain
data on the data object level, not on the data attribute level.
The data set for GOOSE can contain signals on the data
attribute or data object level. Data object level GOOSE
entries can only be received of the following CDC types:
SPS, SPC, ACD, ACT, DPS, DPC, INC, INS, ENC and
ENS.
Up to five report clients can be configured.
One data can be included in the GOOSE data set only once.
[1]
Section 7
139

Advertisement

Table of Contents
loading

Table of Contents