ABB RELION REX640 Engineering Manual page 81

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759117 A
REX640
Engineering Manual
Slot F (SIM).X1-Sensor_I
Slot F (SIM).X2-Sensor_I
Slot F (SIM).X3-Sensor_I
GUID-A3BF6463-0373-4A86-BA2B-4E6DC339596C V1 EN
Figure 49:
All required input connections configured for output
In
Figure
48, the output connection requires more input channels to be connected.
Figure 49
has correction for
input order is according to installation.
When an output is not connected to any function block, Application
Configuration considers the configuration valid. Check validation
warnings from the output pane for possible missing connections.
Once the output is connected, the complete configuration is validated
again.
Example 2:
Slot F (SIM).X4-1;2_VT
GUID-AB99183B-4096-46A0-9CE9-C383EC35C24E V1 EN
Figure 50:
Output connection requiring only one input
Slot F (SIM).X1-Sensor_U
Slot F (SIM).X4-1;2_VT
GUID-3B5E65D5-9129-45D3-967D-338199D48780 V1 EN
Figure 51:
Two output connections requiring two inputs
Protection and control engineering
ILTCTR1
IL1
ALARM
IL2
WARNING
IL3
I3P
IRES_CLC
IRES_CLC_DR
IL1_DR
IL2_DR
IL3_DR
NPS_DR
PPS_DR
O:11|T:2,5|I:1
Figure 48
where all required inputs are configured and the
UTVTR1
UL1
ALARM
UL2
WARNING
UL3
URES_ALARM
MINCB_OPEN
URES_WARNING
URES
U3P
URES_CLC
URES_MEAS
URES_CLC_DR
URES_MEAS_DR
U1_DR
U2_DR
U3_DR
NPS_DR
PPS_DR
FREQ_DR
O:2|T:2,5|I:1
UTVTR1
UL1
ALARM
UL2
WARNING
UL3
URES_ALARM
MINCB_OPEN
URES_WARNING
URES
U3P
URES_CLC
URES_MEAS
URES_CLC_DR
URES_MEAS_DR
U1_DR
U2_DR
U3_DR
NPS_DR
PPS_DR
FREQ_DR
O:2|T:2,5|I:1
Section 5
ILTCTR1[1]_I3P
UTVTR1[1]_URES_MEAS
UTVTR1[1]_U3P
UTVTR1[1]_URES_MEAS
73