Section 6
LHMI engineering
6.1.9
6.1.10
6.1.10.1
122
This action must be confirmed before it is carried out, because it overwrites the
IED's existing display configuration. The writing operation can take a few
seconds or minutes to complete.
3.
To read the configuration from the IED, click the Read from IED button on the
toolbar.
Previewing configuration
After the pages have been configured, the configuration can be previewed with a soft
LHMI before it is written to the IED. The soft LHMI is a Windows version of the
actual LHMI.
•
To launch the soft LHMI and to preview the configuration, click the Show
Preview button.
GUID-BC7D2EB6-D6CC-410C-B73E-0FDF3568C762 V1 EN
Figure 101:
Launching the LHMI preview
GDE configuration export and import
The GDE configuration can be exported and then imported to any other IED.
Exporting GDE configuration
1.
On the File menu, point to Display Editor Template and select Export.
2.
In the GDE Export dialog, select the pages, SLD pages, custom symbols and
translations to be exported.
1MRS759117 A
REX640
Engineering Manual