Section 6
LHMI engineering
118
4.
Place the junction points.
5.
Connect the symbols where necessary by drawing lines between the symbols'
source and destination ports.
GUID-543D7A1C-7DC8-493B-BFE6-1803505A2F26 V1 EN
Figure 98:
Adding symbols to an SLD page
6.
In the Object Properties pane, set the symbol properties.
Use the x and y coordinates to adjust the placement of symbols in the
single-line diagram.
Use controlState to define the default state of the symbol to be displayed
in the view.
Use indicationOnly to define if the symbol is controllable (true = status
only; false = controllable).
Use control to link the symbol to the function block in the application
configuration that protects or controls the object.
Use stateColorMap to specify colors for the different states of the
symbol.
1MRS759117 A
REX640
Engineering Manual