Section 4
Setting up a project
52
1.
In the Plant Structure view, right-click the bay, point to New, point to the relay
application area such as Multiapplication IEDs and select the protection relay
type to be inserted.
Alternatively, drag an IED from the Object Types view to the
bay level.
2.
On the Configuration mode selection page, select Offline configuration and
click Next.
Setting up an IED in the offline mode is similar to the online mode; however,
with the offline mode it is not necessary to type the correct IP address in the IP
address box.
GUID-B4B6B577-1C7B-40C2-BD9B-C5FC5FC087C2 V1 EN
Figure 28:
Selecting the configuration mode
3.
On the Composition code selection page, select the correct composition codes
and click Next.
Ensure that the composition code is correct. PCM600 verifies
that the composition code matches the relay. If the composition
code digits related to the configuration, I/O or version do not
match the relay, PCM600 does not allow writing the
configuration to the relay. If other digits in the composition code