Importing Scd Files - ABB RELION REX640 Engineering Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759117 A
7.3.3.1
REX640
Engineering Manual

Importing SCD files

To be able to import an SCD file at station level, the option IED 61850 configuration
engineering mode enabled has to be cleared in PCM600.
1.
Select the station in the Plant Structure view.
2.
Right-click the station and select Import.
3.
On the open standard Windows menu, select the file to be imported and start the
reading.
GUID-5FC218CD-845E-4F12-8369-A0351234D5A4 V1 EN
Figure 120:
Selecting SCL file import options
4.
In the SCL Import Options dialog box, select how to handle the file during the
import.
Click Don't import IEDs of unknown type to protect the existing IEDs
if the SCD file does not match the original configuration in PCM600.
Click Replace unknown if the file includes additional IEDs that are
needed. The IED of type "Generic IEC 61850 IED" is used to integrate this
kind of IEDs into the plant structure, for example.
Click Ignore PCM Object Type to update the IED objects in PCM600
with the IED types in the SCD file, whether or not the IED types in the SCD
file match the IED objects in PCM600. This option can be used, for
example, when third-party IEDs are included in the system and the SCD
file sends GOOSE messages to ABB IEDs included in the project.
Click Ignore Substation Section to not import the SSD file part of the
SCD file.
5.
Click Import when the file definition has been completed.
A progress view displays the importing procedure.
6.
Make connections from the sending IEDs to the receiving function blocks with
Signal Matrix.
Make connections between the signals that the server sends and the function
blocks on the receiver's side.
7.
Write the configuration to the IED.
In the Plant Structure view, select the IED, right-click and select Write to
IED.
IEC 61850 communication engineering
Section 7
141