Section 7
IEC 61850 communication engineering
7.3.3
140

Importing SCL files to PCM600

The IED engineering tool must be able to receive an SCD file or an ICD file as an
import to receive the engineered communication extensions, for example, for the
different IEDs.
To be able to import an SCD file at station level, the option IED 61850 configuration
engineering mode enabled has to be cleared in PCM600.
1.
On the Tools menu, select Options and click IEC 61850 Configuration.
2.
On the Engineering tab, clear the option IED 61850 configuration
engineering mode enabled and click OK.
GUID-3B18C93E-5450-43B1-823F-02C640D5FCB0 V1 EN
Figure 118:
Enabling SCD file import at station level
If the IED 61850 configuration engineering mode is enabled, SCD files cannot be
imported and an error message is shown.
GUID-F6D95B8F-7DBD-44A2-ABE7-39D8739B252E V1 EN
Figure 119:
Error message when SCD files cannot be imported