Choose the applicable function and trip mode, such as
CB Pos Check .
1.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current
value. Measure time from BFI_3P of CCRBRF (50BF).
2.
Check the re-trip
In applicable cases, the back-up trip for multi-phase pickup
t3 can also be checked. To check t2MPh , a two-phase or three-phase initiation shall be
applied.
3.
Disconnect AC and BFI_3P input signals.
10.5.9.4

Verifying the re-trip mode

Choose the mode below, which corresponds to the actual case.
In the cases below it is assumed that
Checking the case without re-trip,
1.
Set
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current
value.
3.
Verify that no re-trip, but back-up trip is achieved after set time.
4.
Disconnect AC and BFI_3P input signals.
Checking the re-trip with current check,
1.
Set
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current
value.
3.
Verify that re-trip is achieved after set time
4.
Apply the fault condition, including initiation of CCRBRF (50BF), with current below set
current value.
5.
Verify that no re-trip, and no back-up trip is obtained.
6.
Disconnect AC and BFI_3P input signals.
Checking re-trip without current check
1.
Set
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current
value.
3.
Verify that re-trip is achieved after the set time
4.
Apply the fault condition, including initiation of CCRBRF (50BF), with current below set
current value.
5.
Verify that re-trip is achieved after set time
6.
Disconnect AC and BFI_3P input signals.
10.5.9.5
Verifying the back-up trip mode
In the cases below it is assumed that
Commissioning manual
t1 and back-up trip times t2 and t3 .
RetripMode = Retrip Off .
RetripMode = CB Pos Check .
RetripMode = No CBPos Check .
FunctionMode = Current and RetripMode =
FunctionMode = Current is selected.
RetripMode = Retrip Off
RetripMode = CB Pos Check
t1 and back-up trip after time t2
t1 , and the back-up trip after time t2 .
t1 , but no back-up trip is obtained.
FunctionMode = Current is selected.
Testing functionality by secondary injection
t2MPh and back-up trip 2, t2 and
Section 10
M12104-36 v6
M12104-107 v6
M12104-48 v6
M12104-58 v8
M12104-146 v5
151