Section 10
Testing functionality by secondary injection
10.17.1.2

Completing the test

Continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
10.18
Exit test mode
The following procedure is used to return to normal operation.
1.
Navigate to the test mode folder.
2.
Change the
3.
Answer
218
After exiting the IED test mode, make sure that the MU is returned to normal mode.
Enable setting to Disable . Press the 'E' key and the left arrow key.
YES , press the 'E' key and exit the menus.
1MRK 504 154-UUS B
TestMode setting to Disabled .
Commissioning manual
M11369-39 v4
SEMOD53244-3 v4