Completing The Test - ABB RET670 Commissioning Manual

Transformer protection version 2.1 ansi
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 154-UUS B
1.
Inject the polarizing voltage 3V0 to about 90% of the setting (
2.
Activate the CRL binary input.
3.
Increase the injected voltage to about 110% of the setting (
4.
Activate the CRL binary input.
5.
Check that the ECHO, CS and TRWEI appear on the corresponding binary output or on the
local HMI.
6.
Reset the CRL binary input.
7.
Activate the BLOCK binary input.
8.
Activate the CRL binary input.
9.
Reset the CRL and BLOCK binary input.
10.
Inject the polarizing voltage 3V0 to about 110% of the setting (
angle between the voltage and current to (180°-
voltage.
11.
Inject current in one phase to about 110% of the set trip current (
12.
Activate the CRL binary input.
13.
Abruptly reverse the current to 65° lagging the voltage to trip the forward directional
element.
14.
Switch the current off and check that the ECHO, CS and TRWEI appear on the corresponding
binary output during 200ms after resetting the directional element. If EF4PTOC also trips in
forward direction, CS should be obtained.
15.
Switch the polarizing voltage off and reset the CRL binary input.
10.11.2.3

Completing the test

Continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
Commissioning manual
No ECHO, CS and TRWEI outputs should appear.
No ECHO, CS and TRWEI outputs should appear.
No ECHO and TRWEI should appear.
No ECHO and TRWEI should appear.
Testing functionality by secondary injection
3V0PU ) operating voltage.
3V0PU ) operating voltage.
3V0PU> ) and adjust the phase
AnglRCA ) setting, the current leads the
INDir ).
TestMode setting to Disabled .
Section 10
M13936-90 v5
207