Advertisement

1MRK 504 154-UUS B
ANSI07000188 V1 EN-US
Figure 46: Test of RTC with I/O
10.17

Basic IED functions

10.17.1
Parameter setting group handling SETGRPS
Prepare the IED for verification of settings as outlined in section
"Preparing for test"
10.17.1.1
Verifying the settings
1.
Check the configuration of binary inputs that control the selection of the active setting
group.
2.
Browse to the ActiveGroup menu to achieve information about the active setting group.
The ActiveGroup menu is located on the local HMI underMain menu/Test/Function status/
Setting groups/ActiveGroup
3.
Connect the appropriate dc voltage to the corresponding binary input of the IED and observe
the information presented on the local HMI.
The displayed information must always correspond to the activated input.
4.
Check that the corresponding output indicates the active group.
Operating procedures for the PC aided methods of changing the active setting groups are
described in the corresponding PCM600 documents and instructions for the operators
within the SCS are included in the SCS documentation.
Commissioning manual
in this chapter.
Testing functionality by secondary injection
"Requirements"
and section
Section 10
SEMOD52026-1 v1
M11369-2 v3
M11369-4 v4
217