ABB RET670 Commissioning Manual page 128

Transformer protection version 2.1 ansi
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
It
fs
EQUATION14062 V1 EN-US
I
tfs
frequency of
Expected result: the protection function does not issue either start or trip.
The trajectory of the impedance traverses the lens characteristic in zone 2
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/OutOfStep(78,Ucos)/
OOSPPAM(78,Ucos):1/Outputs to check the available service values of the function block
OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related to phase
L1):
V
=
ts
EQUATION14063 V1 EN-US
V
ts
EQUATION14058 V1 EN-US
frequency of V
I
50
s
EQUATION14059 V1 EN-US
I
50s
frequency of
It
fs
EQUATION14062 V1 EN-US
I
tfs
frequency of
Check that the service values (VOLTAGE, CURRENT, R(%), X(%) ) are according to the injected
quantities and that ROTORANG is close to 3.14 rad. For this particular injection the service
values are:
122
I
1
CTs
I
10459
=
×
=
×
tf
I
9000
CTp
= 180º
I
= 49.5 Hz
tfs
V
VT s
,
0 9
.
V
0 9 11931
.
×
×
=
×
t FwdZ
,
V
VT p
,
ForwardX
arctan
arctan
=
 =
ForwardR
= 50 Hz
ts
I
1
CTs
I
10459
=
×
=
×
50
I
9000
CTp
= 0º
I
= 50 Hz
50s
I
1
CTs
I
10459
=
×
=
×
tf
I
9000
CTp
= 0º
I
= 50 Hz
tf
VOLTAGE = 10.74 kV
CURRENT = 20918 A
R = 7.37%
X = 53.40%
ROTORANG = -3.09 rad
1 162
.
A
=
0 1
.
77 81
.
V
×
=
13 8
.
59 33
.
82. . 14°
 =
8 19
.
= .
1 162
A
1 162
.
A
=
1MRK 504 154-UUS B
(Equation 26)
GUID-9F0FE404-6D83-4308-9FE4-13259CE7D07A v1
GUID-700F4EA1-B7D9-4B77-829A-433BB67C8A01 v1
(Equation 27)
(Equation 28)
(Equation 29)
(Equation 30)
Commissioning manual