Section 5
Configuring the IED and changing settings
The primary CT data are entered via the HMI menu under Main menu/Configurations/Analog
modules
The following parameter shall be set for every current transformer connected to the IED:
Table 8:
Parameter description
Rated CT primary current in A
This parameter defines the primary rated current of the CT. For two set of CTs with ratio 1000/1
and 1000/5 this parameter is set to the same value of 1000 for both CT inputs. The parameter
CTStarPoint can be used in order to reverse the direction of the CT. This might be necessary if two
sets of CTs have different neutral (WYE) point locations in relation to the protected busbar.
For main CTs with 2A rated secondary current, it is recommended to connect the secondary wiring
to the 1A input.
5.3

Reconfiguring the IED

I/O modules configured with PCM600 (BIM, BOM or IOM) are supervised.
I/O modules that are not configured are not supervised.
Each logical I/O module has an error flag that indicates signal or module failure. The error flag is
also set when the physical I/O module of the correct type is not detected in the connected slot.
52
CT configuration
Parameter name
CTPRIMn
n = channel number
Take the rated permissive overload values for the current inputs into
consideration.
Range
from 0 to 99999
1MRK 504 154-UUS B
Default
3000
M11728-2 v2
Commissioning manual