1MRK 504 154-UUS B
Section 10
10.1

Testing disturbance report

10.1.1

Introduction

The following sub-functions are included in the disturbance report function:
Disturbance recorder
Event list
Event recorder
Trip value recorder
Indications
If the disturbance report is enabled, then its sub-functions are also set up and so it is not possible
to only disable these sub-functions. The disturbance report function is disabled (parameter
Operation = Disabled ) in PCM600 or the local HMI under Main menu/Settings/IED Settings/
Monitoring/Disturbance report/DRPRDRE:1.
10.1.2

Disturbance report settings

When the IED is in test mode, the disturbance report can be made active or inactive. If the
disturbance recorder is turned on during test mode, recordings will be made. When test mode is
switched off all recordings made during the test session are cleared.
OpModeTest for the control of the disturbance recorder during test mode are located on
Setting
the local HMI under Main menu/Settings/IED Settings/Monitoring/Disturbance report/
DRPRDRE:1.
10.1.3

Disturbance recorder (DR)

Manual Trig can be started at any time. This results in a recording of the actual values from all
A
recorded channels.
Manual Trig can be started in two ways:
The
1.
From the local HMI under Main menu/Disturbance records.
1.1.
1.2.
2.
Open the Disturbance handling tool for the IED in the plant structure in PCM600.
Commissioning manual
Testing functionality by secondary
injection
Enter on the row at the bottom of the HMI called Manual trig.
A new recording begins. The view is updated if you leave the menu and return.
Navigate to General information or to Trip values to obtain more detailed information.