Section 14
Troubleshooting
Indicated result
(Protocol name) Ready
(Protocol name) Fail
(I/O module name)
Ready
(I/O module name)
Fail
14.2

Fault tracing

14.2.1
Internal fault indications
If an internal fault has occurred, the local HMI displays information under Main menu/
Diagnostics/IED status/General
Under the Diagnostics menus, indications of a possible internal failure (serious fault) or internal
warning (minor problem) are listed.
Indications regarding the faulty unit are outlined in table 35.
Table 35:
HMI Signal Name:
INT Fail
INT Warning
ADMnn
BIMnn
BOMn
IOMn
MIMn
RTC
Table continues on next page
232
Possible reason
No problem detected.
Protocol has failed.
No problem detected.
I/O modules has failed.
Self-supervision signals on the local HMI
Status
OFF / ON
OFF / ON
READY / FAIL
READY / FAIL
READY / FAIL
READY / FAIL
READY / FAIL
READY / FAIL
Proposed action
None.
None.
Check that the I/O module has been configured and
connected to the IOP1- block.
If the problem persists, contact your ABB representative for
service.
Description
This signal will be active if one or
more of the following internal signals
are active; INT--LMDERROR, INT--
WATCHDOG, INT--APPERROR, INT--
RTEERROR, or any of the HW
dependent signals
This signal will be active if one or
more of the following internal signals
are active; INT--RTCERROR, INT--
IEC61850ERROR, INT--
TIMESYNCHERROR
Analog input module n failed. Signal
activation will reset the IED
BIM error. Binary input module Error
status. Signal activation will reset the
IED
BOM error. Binary output module
Error status.
IOM-error. Input/Output Module Error
status.
mA input module MIM1 failed. Signal
activation will reset the IED
This signal will be active when there is
a hardware error with the real time
clock.
1MRK 504 154-UUS B
IP8765-1 v1
M11763-2 v7
Commissioning manual