Programming errors If during the programming of the parameters an attempt is made to violate certain limitations,
146 | © 2013 ABB | 1SDH001000R0002 - L7804
the release blocks the saving procedure and signals the error:
Type of error
L Th ≥ S Th
S Th ≥ I Th
L Th ≥ S2 Th
S2 Th ≥ I Th
L Th ≥ D Th
D Th ≥ I Th
D Zone Sel = On while S / S2/ G / Rc = On
S(V) t20 and S(V) I20 error
RQ Q24 > Q25
SYNCHRO parameters error
ROCOF t28 error
And the MCR enabled together
High priority alarm
Rc toroid error
Internal neutral config error
Change nr datalogger with dlogger not
stopped
Reverse pole order error
Programming Session Timeout
Error description
Errors in the adjustment of the protection
thresholds
Errors in the adjustment of the protection
thresholds
Errors in the adjustment of the protection
thresholds
Errors in the adjustment of the protection
thresholds
Errors in the adjustment of the protection
thresholds
Errors in the adjustment of the protection
thresholds
Activation of zone selectivity with
protections S, S2, G or Rc enabled
Incorrect configuration of the protection S(V)
Incorrect configuration of the protection RQ
Error in the parameters of the Ekip
Synchrocheck module
Incorrect configuration of the protection
ROCOF
Simultaneous enabling of the protections I
and MCR
Protection and delay alarms present during
programming
An attempt is made to activate the RC
sensor without Ekip Measuring or RC type
rating plug
It tries to set the internal neutral setting with
a value that is not allowed
Change datalogger parameters with
datalogger active
Change in the parameter "pole order" with a
Half size circuit-breaker.
Timeout for saving data
Ekip Touch protection release | 18 - Self-diagnosis
ABB | SACE Emax 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents