Access from the display With the modules powered, and Local Bus enabled, the presence of the modules on the
203 | © 2013 ABB | 1SDH001000R0002 - L7804
terminal box activates additional menus on the display, to configure the modules according to
the characteristics of the network.
To enable the Local Bus, you need to select "On" in the menu Settings, Modules, Local Bus.
The following table illustrates the path for accessing the configuration parameters of the
modules from the display:
...
Network frequency
Settings
Modules
Power Controller
...
The following table illustrates configuration parameters of the modules:
Parameter
Values
MAC Address
1...63
125 kbit/s,
Baudrate
250 kbit/s,
500 kbit/s
NOTE: the modules can also be configured with the Ekip Connect application (see
the chapter "13 - Other accessories", and the paragraph "Ekip Connect application"
on page 221).
The following table illustrates the path from the display for accessing information on the
modules:
Protection unit
Circuit-breaker
Information
Modules
Power Controller
The information on the modules that can be viewed includes the serial number and the software
version.
Local/Remote
Local Bus
...
Ekip Com DeviceNet
Ekip Com DeviceNet *R
...
Function
Default
Description
• Ekip Com
Address to be assigned to the modules.
DeviceNet: 63
• Ekip Com
IMPORTANT: devices connected
DeviceNet
to the same network must have
Redundant: 62
different addresses.
125 kbit/s
Data transmission speed
...
Ekip DeviceNet
Ekip DeviceNet *R
...
Electronic accessories | 8 - Ekip Com DeviceNet modules
ABB | SACE Emax 2
MAC Address
Baudrate
MAC Address
Baudrate