Ekip Com Profinet Modules; Description; Compatibility And Power Supply; Aup Auxiliary Contacts - ABB SACE Emax 2 Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

10 - Ekip Com Profinet modules

Description The Ekip Com Profinet is a communication accessory module, that integrates the circuit-
Compatibility and power supply The modules can be installed in the presence of Ekip Touch, Hi-Touch, G Touch, and G Hi-
AUP auxiliary contacts The module is always supplied with dedicated AUP auxiliary position contacts, which in the
Ekip RTC contact The module is always supplied with an Ekip RTC auxiliary contact, that supplies the release
210 | © 2013 ABB | 1SDH001000R0002 - L7804
breaker in an industrial remote supervision and control network.
It can be connected to an Ethernet network with a Profinet communication protocol, and
allows you to:
• Connect the releases to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker remotely.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If connected to a circuit-breaker in withdrawable version, detect the connected/extracted.
IMPORTANT: the modules can be connected only to networks that meet all
the necessary requirements for safety and prevention of unauthorised access
(for example, the control system network of an installation). It is responsibility
of the installer to make sure that all the necessary security measures are
adopted (for example, a firewall). Connection is recommended only to dedicated
Ethernet networks, with the Profinet communication protocol. The module
cannot be connected to the Internet.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker
is equipped with an Ekip Com Actuator module (see page 219).
For applications in which a high network reliability is necessary, the module can be installed
along with the corresponding Redundant module.
The Redundant module is identical in terms of specifications and installation methods, but its
wiring is different to the first one.
IMPORTANT: on the same circuit-breaker, a single Ekip Com Profinet, and a
single Ekip Com Profinet Redundant can be installed.
Touch releases, and require the presence of an Ekip Supply module in the first slot of the
circuit-breaker terminal box.
case of a withdrawable circuit-breaker supply the signal for inserted/extracted moving part
from the fixed part.
The assembly assures that the position signalling is also maintained with the moving part
withdrawn.
IMPORTANT: in the presence of multiple communication modules, only one
of these can be connected to the AUP contacts.
with the signal indicating circuit-breaker ready to receive a close command.
Electronic accessories | 10 - Ekip Com Profinet modules