Maximum and minimum
Peak Factor
126 | © 2013 ABB | 1SDH001000R0002 - L7804
currents Path
Main page - Menus - Measurements - History - Measurements
NOTE: for the details on the pages, see the chapter Menu pages and menus, and
the paragraph Measurement history, beginning from page 65.
Description
The maximum and minimum currents are the recordings of the measurements of the maximum
and minimum phase currents performed by the release, and that can be displayed by selecting
I Max and I Min in the menu History - Measurements.
The interval between one measurement and the other can be set through the parameter
Measurement interval, available in the menu History.
The recordings can be reset through the command Reset measurements, available in the
menu History - Measurements.
Correlated information
Every measurement is correlated by the following information:
• The time interval since the previous measurement.
• The phase to which it refers, and value in Amperes.
• The date and time (referring to the internal clock).
• Graphical representation in the form of a histogram on a time axis.
NOTE:
• If the value is less than 0.03 In, "..." is shown instead of the value in Amperes.
• The graphical representation is in reference to 1 In, with a maximum value of 1.25
In
• When the parameter "Measurement interval" is modified, the release performs a
recording immediately.
Path
Main page - Menus - Measurements
Description
The selection of Peak factor in the menu Measurements allows you to display the
measurements in real time of the peak factors of the phase currents.
The measurements are expressed as a ratio between the peak values and RMS values, for
each individual phase.
Ekip Touch protection release | 14 - Touch measurements