Ekip T&P Module; Ekip Tt Module - ABB SACE Emax 2 Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

Ekip T&P module The Ekip T&P module is part of the Ekip T&P programming and test kit for Ekip releases, and

Ekip TT module

222 | © 2013 ABB | 1SDH001000R0002 - L7804
allows you to:
• In the absence of auxiliary voltage, to supply the release.
• With the Ekip Connect application (see page 221), access the information and the pages
for programming the release, and to activate the test pages.
IMPORTANT: Ekip T&P can also be connected to the releases when in service.
In the case of connection to releases in service, it is not possible to perform
an opening test.
NOTE: Ekip T&P only powers the release. Therefore, in order to set and to display
information on any electronic accessories connected to the terminal box, these must
be powered with an Ekip Supply module (see page 162).
It draws its power from the PC, and connects one side directly to the test connector at the front
of the release, and on the other to the USB ports of the PC with the cable supplied.
It turns on after connecting to the PC, and is equipped with two LEDs, a green one indicating
that the module is on, and a yellow one indicating active communication.
Ekip TT is supplied as standard with Ekip Dip releases not mounted on a circuit-breaker, and
with Touch, Hi-Touch, G Touch, and G Hi-Touch releases, and allows the following:
• Make sure that the opening mechanism of the circuit-breaker functions properly, commanding
an opening by pressing the TEST button of the Ekip TT (opening test).
• In the absence of auxiliary voltage and where the circuit breaker is open due to a protection
tripping, power the release so that you can see which protection tripped either on the
display or through the lighting of the corresponding LEDs.
• In the absence of auxiliary voltage, power the Ekip Touch, Hi-Touch, G Touch, and G Hi-
Touch releases in order to set the protections.
IMPORTANT: Ekip TT can also be connected to the releases when in service.
In the case of connection to releases in service, it is not possible to perform
an opening test.
NOTE: the Ekip TT only powers the release. Therefore, in order to set and to display
information on any electronic accessories connected to the terminal box, these must
be powered with an Ekip Supply module (see page 162).
Draws its power from three AA alkaline batteries 1.5V, connects to the test connector at the
front of the trip unit with the supplied cable, and is turned on by setting the side switch to ON.
It includes a led that is green when the device is energized and the batteries are charged, and
red when the batteries are drained and need to be replaced.
Further information on Ekip TT is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular on kit sheet 1SDH001000R0519, and in the Ekip Connect
application manual 1SDH000891R0002.