Aup: Auxiliary Position Contacts - ABB SACE Emax 2 Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

AUP: auxiliary position contacts The AUP contacts are intended for circuit-breakers in withdrawable version.
A4
XF
102
4
S75I/1
A3
XF
A4
233 | © 2013 ABB | 1SDH001000R0002 - L7804
They electrically signal the position of a moving part (inserted/test/withdrawn) in relation to the
fixed part in which they are inserted.
These are "switching" contacts and are available, up to a maximum of 10 contacts per circuit-
breaker, in the following configurations:
• five standard contacts
• five digital signals
• five additional standard contacts
• five additional digital signals
The following table provides information on the electrical characteristics:
Characteristics
DC
Breaking
capacity
AC
Minimum load
AUP: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
104
112
114
122
124
132
2
4
2
S75I/2
1
1
2
4
S75T/1
1
2
S75E/1
101
111
121
Diagrams 96 - 97
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0603.
Standard
24V
-
125V
0.5A @ 0ms / 0.3A @ 10ms
250V
0.3A @ 0ms / 0.15A @ 10ms -
3A cos φ 0,3
5A cos φ 0,7
250V
5A cos φ 1
3A cos φ 1
400V
2A cos φ 0,7
1A cos φ 0,3
50mA @ 24V
96
152
134
142
144
4
S75I/3
4
2
4
S75E/2
1
1
131
141
Digital signals
0.1 A
-
-
-
-
-
-
-
1mA @ 5V
154
162
164
172
174
182
2
4
2
S75I/4
1
1
2
4
S75T/2
1
2
S75E/3
151
161
171
Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
97
184
192
194
4
2
4
S75E/4
1
1
181