Table 3-3
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Max. connectable cross-section 1.5 mm²; type: Screw terminal
Technical data for X331:
1
● Max. output voltage: Infeed voltage at X310.3 minus approx. 2 V
● Max. load current per output: 200 mA, continuously short-circuit-proof
● Output delay:
Technical data for X332:
2
● Voltage range: -10 to 10 V, continuously short-circuit-proof
● Max. load current per output: 3 mA
● Resolution: 12-bit
Technical data for X333:
3
Pt100 temperature sensors use the four wire measurement principle. For a two-wire
measurement, you must jumper terminal I_OUT n with TEMP n+, and TEMP n- with I_IN n.
SINAMICS SM120 6SL38855?B
Operating Instructions 12/2015
Power Stack Adapter 4: Analog and digital outputs and temperature sensor connections
X331
1
M
DO 7
DO 6
M
M
DO 5
DO 4
M
M
DO 3
DO 2
M
M
DO 1
DO 0
M
– For "0" to "1": Typ. 100 μs for 0.2 A resist. load
– For "1" to "0": Typ. 10 μs for 0.2 A resist. load
X332
2
AO 7-
AO 7+
AO 6+
AO 6-
AO 5-
AO 5+
AO 4+
AO 4-
AO 3-
AO 3+
AO 2+
AO 2-
AO 1-
AO 1+
AO 0+
AO 0-
Description
3.4 Components
X333
3
I_IN 3
TEMP 3-
TEMP 3+
I_OUT 3
I_IN 2
TEMP 2-
TEMP 2+
I_OUT 2
I_IN 1
TEMP 1-
TEMP 1+
I_OUT 1
I_IN 0
TEMP 0-
TEMP 0+
I_OUT 0
37