Siemens SINAMICS SM120 Operating Instructions & Installation Instructions page 113

Motor module
Hide thumbs Also See for SINAMICS SM120:
Table of Contents

Advertisement

Final checks
1. Make sure that all the screws have been tightened with the correct torques.
2. Check whether all of the couplings of the cooling water connections are correctly inserted
Resetting the bypass marking
When the bypass has been triggered, the double submodule is electronically marked. After
installing a new double submodule, including bypass, you must reset this marking. Proceed
as follows:
1. Select the p6112 parameter in the AOP or STARTER.
2. Enter the number of the replaced double submodule. The numbering of the double
3. Select parameter p6113. Set the value to "0". This will reset the electronic marking.
SINAMICS SM120 6SL38855?B
Operating Instructions 12/2015
NOTICE
Damage and/or short-circuits at the double submodules
If you do not comply with the screw torques, then this can lead to damage and/or short-
circuits at the double submodules.
When installing the double submodules comply with the specified torques.
Screw type
M4
M5
M8
and interlocked (shift the plastic ring towards the front and insert the locking ring).
NOTICE
Locking ring not inserted
The gating unit can be damaged if the flow of water through the heatsink is not guaranteed.
In order to guarantee a reliable flow of water through the heat sink, the locking ring must
be correctly inserted. After the water coupling has been interlocked, insert the locking ring
into the slot between the locking ring and the coupling.
If the locking ring cannot be inserted, then check whether the water coupling is correctly
inserted and interlocked.
Note
Ventilating the deionized water circuit
After replacing the double submodule, the deionized water circuit must be ventilated.
submodule is identical to the number of the alarm value of alarm A30203.
Torque
1.8 Nm
3 Nm
For the M5 x 25 screws of the upper holding rail, a torque of 6 Nm
must be used (see step 4 of the description on removing).
13 Nm
Maintenance
9.7 Repair
113

Hide quick links:

Advertisement

Table of Contents
loading