3.
Tighten all the 8-32 x 5/16-in. screws to a torque of 15 in-lbs. (17 cm-kgs).
FIGURE 40 Attaching the rear bracket to the device
1.
Screws, 8-32 x 5/16-in., panhead Phillips
Installing the Universal Four-Post Rack Kit (XBR-
R000296)
Use the following instructions to install 1U and 2U devices in EIA racks that are between L-12.7 to 81.28 cm deep (L-5.0 to 32.0 in.),
where L is the chassis depth, using the Universal Four-Post Rack Kit (XBR-R000296).
There are two ways you can mount the device in a four-post rack:
With the port side flush with the front posts.
With the nonport side flush with the rear posts in a recessed position. A recessed position allows a more gradual bend in the
fiber-optic cables connected to the switch and less interference in the aisle at the front of the rack.
TABLE 1 Space requirements
Chassis with port-side
Notes
side vents
No
Applicable to port-side and nonport-side flush
mounts.
Yes
Applicable to port-side flush mounts.
Yes
Applicable to nonport-side flush mounts.
Note that if chassis depth (L) is less than 40.64 cm (16 in.), the chassis will not fit into a rack with a maximum depth of 81.28 cm (32 in.)
using the universal four-post rack kit. The maximum rack depth for a chassis less than 40.64 cm (16 in.) is 81.28 cm (32 in.) minus the
difference between the chassis depth and 40.64 cm (16 in.). For example, a chassis with a depth (L) of 35.56 cm (14 in.) is 5.08 cm (2
ExtremeSwitching VDX 6740 Hardware Installation Guide
9036108-00

Installing the Universal Four-Post Rack Kit (XBR-R000296)

Chassis depth
Minimum rack depth
L
L-12.7 cm (L-5 in.)
L
L-12.7 cm (L-5 in.)
L
L
Maximum rack depth
81.28 cm (32 in.)
81.28 cm (32 in.)
81.28 cm (32 in.)
61