How to set the PROFIBUS-DP address at the ECOFAST terminal block
Valid range of the PROFIBUS DP addresses: 1 to 99. If you select a higher
address, the I/O module will return an error signal via the red bus error LED.
1. Unscrew and remove the configuration module from the ECOFAST terminal
block.
Figure 2-5
2. Unscrew and remove the cap of the configuration module.
3. Set the PROFIBUS address on the DIL switches.
Figure 2-6
4. Screw on the cap again. Reinsert the configuration module and fasten it on the
terminal block with the screws.
2-8

How to unscrew the configuration module

2

How to set the PROFIBUS address at the configuration module

1
Example: PROFIBUS address 92
2
3
4
6
2
+ 2
+ 2
+ 2
= 4 + 8 + 16 + 64 = 92