Danfoss VLT AQUA Drive FC 202 Design Manual page 52

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
®
VLT
AQUA Drive FC 202
High/normal load
(High overload=150% current during 60 s, normal
overload=110% current during 60 s)
Typical shaft output at 525 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 525 V) [A]
Intermittent (60 s overload) (at 525 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 525 V) [kVA]
Continuous kVA (at 575 V) [kVA]
7
7
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 525 V) [A]
Continuous (at 575/690 V) [A]
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Brake or regeneration [mm
Maximum number and size of cables per phase (E3h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Load share or regeneration [mm
Maximum external mains fuses [A]
Estimated power loss at 600 V [W]
Estimated power loss at 690 V [W]
3)
Efficiency
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C (°F)]
Table 7.10 Electrical Data for Enclosures E1h/E3h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 7.5 Ambient Conditions. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
50
®
VLT
AQUA Drive FC 202
2
(AWG)]
2
(AWG)]
2
(AWG)]
2
(AWG)]
2
(AWG)]
2
(AWG)]
1)
2), 3)
2), 3)
Danfoss A/S © 01/2018 All rights reserved.
N560
HO
NO
400
450
500
600
500
560
E1h/E3h
523
596
785
656
500
570
750
627
498
568
498
568
598
681
504
574
482
549
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
6833
8076
6678
7852
0.98
0–500
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
± 15% (tolerance relates to variety in voltage and cable conditions). These
N630
HO
NO
450
500
600
650
560
630
E1h/E3h
596
630
894
693
570
630
855
693
568
600
568
627
681
753
574
607
549
607
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
8069
9208
7848
8921
0.98
0–500
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
MG22B222