Danfoss VLT AQUA Drive FC 202 Design Manual page 178

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Electrical Installation Con...
These values are true to steady state operation and at RMS input voltage range of the drive V
braking mode, the intermediate DC-link voltage increases by 20%. This effect is similar to increasing the mains voltage by
20%. Consider this voltage increase when performing motor insulation analysis for braking applications.
3.50
3.00
2.50
2.00
1.50
1.00
0.50
0
1
Unshielded cable with no filter
2
Shielded cable with no filter
3
Unshielded cable with dU/dt filter
4
Shielded cable with dU/dt filter
10
10
Figure 10.17 dU/dt at Motor Terminals for Enclosures E1h/E3h,
380–480 V
176
1
2
3
4
100
200
(328)
(656)
Motor cable length, m (ft)
®
VLT
AQUA Drive FC 202
300
(984)
1
2
3
4
Figure 10.18 Peak Voltages at Motor Terminals for Enclosures
E1h/E3h, 380–480 V
Danfoss A/S © 01/2018 All rights reserved.
. When the drive operates in
line
1
3.00
2.50
2.00
2
3
1.50
1.00
0.50
0
100
(328)
Motor cable length, m (ft)
Unshielded cable with dU/dt filter
Shielded cable with dU/dt filter
Shielded cable with no filter
Unshielded cable with no filter
4
200
300
(656)
(984)
MG22B222