Danfoss VLT AQUA Drive FC 202 Design Manual page 156

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Mechanical Installation Con...
9.6.3 Derating for Ambient Temperature and Switching Frequency
NOTICE!
FACTORY DERATING
Danfoss drives are already derated for operational temperature (55 °C (131 °F) T
Use the graphs in Table 9.4 to Table 9.5 to determine if the output current must be derated based on switching frequency
and ambient temperature. When referring to the graphs, I
indicates the switching frequency.
Enclosure
D1h–D8h
N90 to N250
380–480 V
9
9
E1h–E4h
N315 to N500
380–480 V
Table 9.4 Derating Tables for Drives Rated 380–480 V
154
Switching
High overload HO, 150%
pattern
60 AVM
110
100
90
80
70
60
0
1
2
3
SFAVM
110
100
90
80
70
60
0
1
2
60 AVM
110
100
90
80
70
60
0
1
2
SFAVM
110
100
90
80
70
60
0
1
Danfoss A/S © 01/2018 All rights reserved.
®
VLT
AQUA Drive FC 202
indicates the percentage of rated output current, and fsw
out
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
9
4
5
6
7
8
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
3
4
5
6
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
3
4
5
6
7
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
2
3
4
5
and 50 °C (122 °F) T
AMB,MAX
Normal overload NO, 110%
110
100
90
80
70
60
50
0
1
2
3
4
5
6
110
100
90
80
70
60
50
0
1
2
3
4
110
100
90
80
70
60
50
0
1
2
3
4
110
100
90
80
70
60
50
0
1
2
3
).
AMB,AVG
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
7
8
9
40 ˚C (104 ˚F)
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
5
6
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
5
6
7
40 ˚C (104 ˚F)
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
4
5
MG22B222

Advertisement

Table of Contents
loading

Table of Contents