Danfoss VLT AQUA Drive FC 202 Design Manual page 49

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
®
VLT
AQUA Drive FC 202
High/normal overload
(High overload=150% current during 60 s, normal overload=110%
current during 60 s)
Typical Shaft output at 525 V [kW]
Typical Shaft output at 575 V [hp]
Typical Shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 525 V) [A]
Intermittent (60 s overload) (at 525 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 525 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 525 V) [A]
Continuous (at 575/690 V)
Maximum number and size of cables per phase
- Mains, motor, brake, and load share [mm
Maximum external mains fuses [A]
Estimated power loss at 575 V [W]
Estimated power loss at 690 V [W]
Efficiency
3)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Table 7.7 Electrical Data for Enclosures D2h/D4h/D7h/D8h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 7.5 Ambient Conditions. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
MG22B222
Design Guide
2
(AWG)]
1)
2), 3)
2), 3)
Danfoss A/S © 01/2018 All rights reserved.
N200
HO
NO
132
160
200
250
160
200
D2h/D4h/D7h/D8h
201
253
301
278
192
242
288
266
183
230
191
241
229
289
193
244
185
233
2x185 (2x350)
550
2361
3074
2446
3175
0.98
0–590
110 (230)
80 (176)
± 15% (tolerance relates to variety in voltage and cable conditions). These
N250
HO
NO
160
200
250
300
200
250
253
303
380
333
242
290
363
319
230
276
241
289
289
347
244
292
233
279
2x185 (2x350)
550
3012
3723
3123
3851
0.98
0–590
110 (230)
80 (176)
47
7
7