Danfoss VLT AQUA Drive FC 202 Design Manual page 186

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Electrical Installation Con...
1
2
3
10
10
4
5
1
PLC
2
Minimum 16 mm
3
Control cables
4
Minimum 200 mm (7.9 in) between control cables, motor
cables, and mains cables.
5
Mains supply
6
Bare (unpainted) surface
7
Star washers
8
Brake cable (shielded)
9
Motor cable (shielded)
Figure 10.27 Example of Proper EMC Installation
184
L1
L2
L3
PE
2
(6 AWG) equalizing cable
®
VLT
AQUA Drive FC 202
90
4
4
10
Mains cable (unshielded)
11
Output contactor
12
Cable insulation stripped
13
Common ground busbar. Follow local and national
requirements for cabinet grounding.
14
Brake resistor
15
Metal box
16
Connection to motor
17
Motor
18
EMC cable gland
Danfoss A/S © 01/2018 All rights reserved.
6
7
8
9
10
11
12
13
14
15
u
16
v
w
PE
17
18
MG22B222

Advertisement