5
Check for tightness of connectors!
Screws of unused terminals must be tightened!
For the electrical connection of the Q2, please refer to the following list:
Connector
TB1-1
+24 VDC
TB1-2
(GROUNDING)
TB1-3
0 VDC
TB2-1
TB2-2
TB2-3
TB2-4
TB3-1
E_RX+
TB3-2
E_RX-
TB3-3
E_TX+
TB3-4
E_TX-
TB4-1
RS485_1GND
TB4-2
RS485_1+
TB4-3
RS485_1-
TB4-4
RS485_2GND
TB4-5
RS485_2+
TB4-6
RS485_2-
TB5-4
DI_1+
TB5-3
DI_1-
TB5-2
DI_2+
TB5-1
DI_2-
TB6-5
DO_1
TB6-4
DO_2
TB6-3
DO_3
TB6-2
DO_4
TB6-1
DO_COM
TB7-5
AO_1
TB7-4
AO_2
TB7-3
AO_3
TB7-2
AO_4
TB7-1
AO_COM
Page 40 of 135
Configuration / Signals
Use only with PELV
+ receive line
- receive line
+ transmit line
- transmit line
ground
+ data line
- data line
ground
+ data line
- data line
+ signal line
- signal line
+ signal line
- signal line
switch signal, normally closed (NC)
switch signal, normally open (NO)
switch signal, normally open(NO)
switch signal, normally open (NO)
common ground
current signal
current signal
current signal
current signal
common ground
G a s Q u a l i t y A n a l y z e r
Transport, storage, installation
Interface
Power supply
(see also chapter 2.3)
Future use
Ethernet port
10/100 Mbit/s
Galvanic isolation Distance
up to 100 m
RS485 port 1
Galvanic isolation Distance
up to 500 m
RS485 port 2
Galvanic isolation Distance
up to 500 m
Digital input 1
Dev. powered max. 9 V
Galvanic isolation
Digital input 2
Dev. powered max. 9 V
Galvanic isolation
4 Digital outputs
Galvanic isolation
Common ground
(Semiconductor circuit
operates as a potential-
free contact)
max.120 mA at 28,8V (DC)
4 Analog outputs
0/4...20 mA
Galvanic isolation
Common ground
Short circuit protection
R max = 390 Ω