Specifications
D6h frame
D8h frame (not including the N250T5)
D8h frame (N250T5 only)
Table 8.9 Adjustable Frequency Drive Supplied with a Contactor
1) With a Bussmann type LPJ-SP or Gould Shawmut type AJT fuse. 450 A max fuse size for D6h and 900 A max fuse size for D8h.
2) Must use Class J or L branch fuses for UL approval. 450 A max fuse size for D6h and 600 A max fuse size for D8h.
8.8 Connection Tightening Torques
Tighten with the correct torque when tightening all electrical connections. Too low or too high torque results in a bad
electrical connection. To ensure correct torque, use a torque wrench.
Enclosure size
Terminal
D1h/D3h/D5h/D6h
Line power
Motor
Load sharing
Regen
Ground
Brake
Heatsink access panel
D2h/D4h/D7h/D8h
Line power
Motor
Regen
Load sharing
Ground
Brake
Heatsink access panel
Table 8.10 Torque for Terminals
8.9 Power Ratings, Weight and Dimensions
Enclosure size
90–132 kW
(380–500 V)
Rated power [kW]
90–132 kW
(525–690 V)
IP
NEMA
Type 1/12
Shipping
Height
dimensions [mm
Width
(inch)]
Depth
Adjustable
Height
frequency drive
Width
dimensions [mm
Depth
(inch)]
Maximum weight [kg (lb)]
Table 8.11 Power Ratings, Weight, and Dimensions, Enclosure Size D1h-D4h
MG34U422
Instruction Manual
415 V
IEC
100000 A
100000 A
100000 A
D1h
D2h
160–250 kW
90–132 kW
(380–500 V)
(380–500 V)
160–315 kW
37–132 kW
(525–690 V)
(525–690 V)
21/54
21/54
Type 1/12
587 (23)
587 (23)
587 (23)
997 (39)
1170 (46)
997 (39)
460 (18)
535 (21)
460 (18)
893 (35)
1099 (43)
909 (36)
325 (13)
420 (17)
250 (10)
378 (15)
378 (15)
375 (15)
98 (216)
164 (362)
98 (216)
Danfoss A/S © 06/2015 All rights reserved.
480 V
1)
2)
UL
100000 A
100000 A
Consult factory
Torque [Nm (in-lbs)]
19–40 (168–354)
8.5–20.5 (75–181)
2.27 (20)
19–40 (168–354)
8.5–20.5 (75–181)
2.27 (20)
D3h
D4h
160–250 kW
(380–500 V)
160–315 kW
(525–690 V)
20
20
Chassis
Chassis
587 (23)
1170 (46)
535 (21)
1122 (44)
350 (14)
375 (15)
164 (362)
600 V
690 V
2)
1)
UL
IEC
100000 A
100000 A
100000 A
100000 A
Not applicable
Bolt size
M10
M8
M10
M8
D3h
D4h
With regeneration or load share
terminals
20
20
Chassis
Chassis
587 (23)
587 (23)
1230 (48)
1430 (56)
460 (18)
535 (21)
1004 (40)
1268 (50)
250 (10)
350 (14)
375 (15)
375 (15)
108 (238)
179 (395)
8
8
71