Danfoss VLT AutomationDrive FC 302 Instruction Manual page 47

0–315 kw d-frame
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Application Set-up Examples
6.2.5 RS485
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
RS-485
06
61
+
68
69
-
Table 6.11 RS485 Network Connection
MG34U422
Instruction Manual
Parameters
Function
Setting
Parameter 8-30
Protocol
FC*
Parameter 8-31
1*
Address
Parameter 8-32
9600*
Baud Rate
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above-
mentioned parameters.
D IN 37 is an option.
Danfoss A/S © 06/2015 All rights reserved.
6.2.6 Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.12 Motor Thermistor
Parameters
Function
Setting
Parameter 1-90
[2]
Motor Thermal
Thermistor
Protection
trip
Parameter 1-93 T
[1] Analog
hermistor Source
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
parameter parameter 1-90 Motor
Thermal Protection should be
set to [1] Thermistor warning.
D IN 37 is an option.
45
6
6