Specifications
Enclosure size
Description
D5h
D1h ratings+disconnect and/or brake chopper
D6h
D1h ratings+contactor and/or circuit breaker
D7h
D2h ratings+disconnect and/or brake chopper or oversized wiring
cabinet
D8h
D2h ratings+contactor and/or circuit breaker
Table 8.4 D5h–D8h Weights

8.2 Line Power Supply

Line power supply (L1, L2, L3)
Supply voltage
AC line voltage low/line voltage drop-out:
During low AC line voltage or a line drop-out, the adjustable frequency drive continues until the DC link voltage drops below the
minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated supply voltage.
Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency drive's lowest
rated supply voltage.
Supply frequency
Maximum imbalance temporary between line power phases
True power factor (λ)
Displacement power factor (cos Φ) near unity
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480/600 V

8.3 Motor Output and Motor Data

Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
* Dependent on voltage and power
Torque characteristics
Starting torque (constant torque)
Starting torque
Overload torque (constant torque)
Percentage relates to the adjustable frequency drive's nominal torque

8.4 Ambient Conditions

Environment
Enclosure size D1h/D2h/D5h/D6h/D7h/D8h
Enclosure type D3h/D4h
Vibration test all enclosure types
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at SFAVM switching mode)
- with derating
MG34U422
Instruction Manual
5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
Danfoss A/S © 06/2015 All rights reserved.
Maximum weight [kg (lbs.)]
166 (255)
129 (285)
200 (440)
225 (496)
380–500 V ±10%, 525–690 V ±10%
3.0% of rated supply voltage
≥0.9 nominal at rated load
maximum 1 time/2 minutes
Overvoltage category III/pollution degree 2
0–100% of supply voltage
maximum 160% for 60 s *
maximum 180% up to 0.5 s*
maximum 160% for 60 s*
IP21/Type 1, IP54/Type12
maximum 55 °C (131 °F)
50/60 Hz ±5%
8
8
(>0.98)
0–590 Hz*
Unlimited
0.01–3600 s
IP20/Chassis
1.0 g
class Kd
65