Application Set-up Examples
6.2.7 SLC
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
6
6
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
46
®
VLT
AutomationDrive FC 302
Parameters
Function
Setting
Parameter 4-30
[1] Warning
Motor Feedback
Loss Function
Parameter 4-31
100 RPM
Motor Feedback
Speed Error
Parameter 4-32
5 s
Motor Feedback
Loss Timeout
Parameter 7-00
[2] MCB
Speed PID
102
Feedback Source
Parameter 17-11
1024*
Resolution (PPR)
Parameter 13-00
[1] On
SL Controller
Mode
Parameter 13-01
[19]
Start Event
Warning
Parameter 13-02
[44] Reset
Stop Event
key
Parameter 13-10
[21]
Comparator
Warning
Operand
no.
Parameter 13-11
[1] ≈*
Comparator
Operator
Parameter 13-12
90
Comparator
Value
Parameter 13-51
[22]
SL Controller
Comparato
Event
r 0
Parameter 13-52
[32] Set
SL Controller
digital out
Action
A low
Parameter 5-40
[80] SL
Function Relay
digital
output A
*=Default Value
Danfoss A/S © 06/2015 All rights reserved.
Notes/comments:
If the limit in the feedback monitor
is exceeded, Alarm 90, Feedback
monitor is issued. The SLC monitors
Alarm 90, Feedback monitor and if
becomes TRUE, relay 1 is triggered.
External equipment may then
indicate that service may be
required. If the feedback error goes
below the limit again within 5 s,
the adjustable frequency drive
continues and the warning
disappears. But relay 1 is still
triggered until pressing [Reset] on
the LCP.
Table 6.13 Using SLC to Set a Relay
6.2.8 Mechanical Brake Control
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 6.14 Mechanical Brake Control (Open-loop)
Parameters
Function
Setting
Parameters
Function
Setting
Parameter 5-40
[32] Mech.
Function Relay
brake ctrl.
Parameter 5-10
[8] Start*
Terminal 18
Digital Input
Parameter 5-11
[11] Start
Terminal 19
reversing
Digital Input
Parameter 1-71
0.2
Start Delay
Parameter 1-72
+
[5] VVC
/
Start Function
FLUX
Clockwise
Parameter 1-76
I
m,n
Start Current
Parameter 2-20
App.
Release Brake
dependent
Current
Parameter 2-21
Half of
Activate Brake
nominal slip
Speed [RPM]
of the motor
*=Default Value
Notes/comments: