Application Set-up Examples
Speed
Reference
Start ( 18)
Freeze ref ( 27)
Speed up ( 29 )
Speed down ( 32 )
Figure 6.1 Speed Up/Down
6.2.3 Start/Stop
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.7 Start/Stop Command with Safe Stop Option
Speed
Start (18)
Figure 6.2 Start/Stop Command with Safe Stop
MG34U422
Instruction Manual
Parameters
Function
Setting
Parameter 5-10
[8] Start*
Terminal 18
Digital Input
Parameter 5-12
[0] No
Terminal 27
operation
Digital Input
Parameter 5-19
[1] Safe Stop
Terminal 37 Safe
Alarm
Stop
* = Default Value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
D IN 37 is an option.
Danfoss A/S © 06/2015 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.8 Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Figure 6.3 Latched Start/Stop Inverse
Parameters
Function
Setting
Parameter 5-10
[9] Latched
Terminal 18
Start
Digital Input
Parameter 5-12
[6] Stop
Terminal 27
Inverse
Digital Input
* = Default Value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
D IN 37 is an option.