4. Set the Reset Threshold value and Alarm State Change Delay value.
5. Click Save.
Power Input phases
Procedure
1. In the Input Phases tab of PDU Thresholds page, click the Edit pencil icon for the PDU input current and
voltage phases.
2. Set the current and voltage phase threshold values for High Critical, High Warning, Low Warning, and Low
Critical for each phase.
3. Enable the threshold values to receive the alarms.
4. Set the Reset threshold and alarm state change delay value.
5. Click Save.
Circuit breaker
Procedure
1. In the PDU Thresholds Circuit Breaker tab, click the Edit pencil icon to set the circuit breaker threshold for
each Load Segment.
2. Set the threshold values for High Critical, High Warning, Low Warning, or Low Critical.
3. Enable the threshold values to trigger the alarms.
4. Set the Reset threshold and alarm state change delay value.
5. Click Save.