Connecting A Rope Fluid Leak Sensor - HP HPE G2 Series User Manual

Metered, switched, and metered & switched power distribution unit
Table of Contents

Advertisement

4. Use the RJ45 quick disconnect coupler and an Ethernet cable to extend the length of the sensor input
cable and/or to serve as an easy disconnect point for the rack door removal.
5. Plug the sensor cable (or the connected Ethernet cable) into the Sensor-1 or Sensor-2 port on the PDU.

Connecting a rope fluid leak sensor

Procedure
1. Connect the RJ45 jack on the rope fluid leak sensor assembly to a sensor port on the PDU.
2. Thread the rope fluid leak sensor cable through the rack and along the desired path of detection.
3. Secure the rope fluid leak sensor cable to the rack and ground using the cable ties and/or adhesive
mounting strips provided.
NOTE: This kit includes one 6m (19.69 ft) leak sensor rope. More length can be added using option kit
P9T09A (includes one 6m (19.69 ft) leak sensor rope extension). Up to four of the 6m (19.69 ft) length leak
sensor rope extensions can be connected together for a total of 30m (98.43 ft).
NOTE: The wire mount, as illustrated below, is for installation on the floor or ground surface. The wire
mount must be used in the detection area.
114
Connecting and configuring optional hardware